GF333BM 150A 600V Modular three phase reference standard meter

Modular three phase reference meter

The model GF333BM is designed for one modular three phase multi-function reference standard meter, test three phase energy meters and single phase electricity meters, work in the laboratory or meter test bench, convenient for secondary development and Application. It can be as one of the most versatile high precision reference instruments.

 

Features

  • High accuracy up to 0.02%
  • Wide testing range: voltage 0V-600V, current 1mA-150A
  • Testing type: 3 phase 4 wire, 3 phase 3 wire
  • Testing mode: active power, reactive power, apparent power
  • 2-128th Harmonic analysis function
  • Waveform display function
  • Vector diagram function
  • Energy accumulating function
  • Internal pulse input port, testing meter’s error directly
  • Applied to energy meter test bench
 

Parameters

Electrical parameters 
Accuracy 0.05%, 0.04%, 0.02%
Voltage supply 220V±10% or 110V±10%, 50/60Hz
Voltage measurement
Range 0V-600V
Error ±0.02% (50V-600V), ±0.05% (5V-50V)
Display range 0.000000V-600.0000V
Harmonic 2nd-128st
Current measurement
Range 1mA-60A; 1mA-120A; 1mA-150A; 1mA-200A
Error ±0.02% (0.2A-240A), ±0.05% (10mA-0.2A)
Display range 1.000000mA-240.0000A
Power measurement
Active power ±0.02% (0.2A-240A)
±0.05% (0.01A-0.2A)
±0.1% (0.001A-0.01A)
Reactive power ±0.05% (0.2A-240A), ±0.1% (0.001A-0.2A)
Apparent power ±0.05% (0.2A-240A), ±0.1% (0.001A-0.2A)
Energy error
Active energy ±0.02% (0.2A-240A)
±0.05% (0.01A-0.2A)
±0.1% (0.001A-0.01A)
Reactive energy ±0.05% (0.2A-240A), ±0.1% (0.001A-0.2A)
Apparent energy ±0.05% (0.2A-240A), ±0.1% (0.001A-0.2A)
Phase measurement
Range 0°-360°
Error ±0.005°
Display range 0.0001°-359.99°
Frequency measurement
Range 45-65Hz
Display range 45.0000-65.0000
Accuracy 0.001Hz
Power Factor measurement
Range -1.0 ~ 0 ~ +1.0
Resolution 0.0001
Accuracy 0.0005
Energy pulse
High frequency output(CH) 25000Hz
Low frequency output(CL) 5000Hz
Pulse ratio 1:1
Output level 5V
Input level 5V
Input frequency Max. 1MHz
Mechanical parameters 
Dimensions (W×D×H) (mm) 280x200x85 
Weight (kg) 8
Environmental conditions 
Ambient temperature -10°C to 45°C
Influence of external fields ≤0.05 %/mT
Relative humidity 10% to 80%

Download Catalogue