The LC-2KV automatic transformer oil tan delta tester designed and manufactured according to GB/ T5654-2007 "measurement of relative capacitance, tan delta and dc resistivity of liquid insulation materials". Used for measuring tan delta and dc resistivity of insulating liquid dielectric such as insulating oil. Integrated structure. Internal integration of tan delta oil cup, temperature controller, temperature sensor, tan delta test bridge, ac test power source, standard capacitor, high resistance meter, dc high voltage source and other main components. The LC-2KV oil tan delta tester is equipped with a 5.7 inch TFT pure color LCD touch screen and a English menu. The test results can be stored and printed out automatically. The operator can use it skillfully without professional training.
Electrical parameters | |
---|---|
Power supply | AC 220V±10% or 110V±10%, 50/60Hz AC |
Test AC voltage output range | 200-2200V |
Test DC voltage output range | 0-500V |
Accuracy | 2% |
Tan Delta | |
Measurement range | 1x10-6 to 100 |
Resolution | 1×10-6 |
Accuracy | ±1% reading ±1 × 10-5 |
Capacitance | |
Measurement range | 5pF - 200pF |
Resolution | 0.01pF |
Accuracy | ± 1% reading ± 0.5pF |
Relative Permittivity | |
Measurement range | 1 to 30 |
Resolution /td> | 0.01 |
Accuracy | ± 0.5% |
Resistivity Measurement | |
Measurement range | 2.5 MΩm to 100 TΩm |
Resolution | 0.01 |
Accuracy | 2% |
Test Temperature | |
Range | 0°C to 120°C |
Resolution | 0.1°C |
Accuracy | ± 1°C |
Programmable | Yes |
LCD | 5.7 inch touch TFT LCD |
Communication | RS232 and USB port |
IP Rating | IP30 |
Storage data | 1000 sets |
Printer | Internal installed 58mm wide thermal printer. |
Standard | IEC 61326, IEC61010, GB/ T5654-2007, IEC 60247, ASTM D924-08 or D1169:2002 |
Mechanical parameters | |
Dimension (L×W×H)(mm) | 460×370×330 |
Weight (kg) | 42 |
Environmental conditions | |
Operating temperature | -10°C to 50°C |
Storage temperature | -40°C to 70°C |
Relative humidity | ≤90%RH non-condensing |