The outdoor instrument current transformers LZZW3-35Q are fully enclosed and cast in epoxy resin. Instrument transformer is equipped with one core and coil assembly rated for measurement and protection, and then output multi ratio. The current transformers are designed for electric power systems of 50Hz/60Hz rated frequency and 35kV rated voltage. They are used for outdoor mounting. The performances of the products meet standards IEC60044-1, IEC61869-2 and ANSI/IEEE C57.13. The products are applied to metering electric energy, voltage controlling and relay protection.
Rated primary current (A) | Accuracy class combination | Rated secondary output (VA) | Surface creepage distance (MM) |
Weight (KG) | ||||
---|---|---|---|---|---|---|---|---|
1S/2S | 0.2(S)0.5S | 0.5 | 5P10 | 5P15 | 5P20 | |||
10-630 | 0.2(S)/0.5(S) 0.2(S)/5p 0.5(S)/5p |
10 | 20 | 100 | 60 | 40 | 1300 |
90 |
750-2000 | 120 | 75 | 50 |
Rated primary current(A) | Accuracy class combination | Rated secondary output(VA) | Surface creepage distance (MM) |
Weight(KG) | ||||
---|---|---|---|---|---|---|---|---|
1s/2s/3s | 0.2(s)0.5S | 0.5 | 5P10 | 5P15 | 5P20 | |||
10-500 | 0.2(S)/0.2(S)/5P 0.2(S)/0.5(S)/5p 0.5(S)/0.5(S)5p |
10 | 20 | 50 | 30 | 25 | 1300 |
90 |
600-1000 | 80 | 50 | 30 | |||||
1200-2000 | 100 | 60 | 40 | |||||
100-630 | 0.2(S)/5p/5p 0.5(S)/5p/5p |
10 | 20 | 30 | 20 | 15 | ||
750-1000 | 50 | 30 | 20 | |||||
1200-1600 | 60 | 30 | 25 | |||||
2000 | 60 | 40 | 25 |
Rated primary current (A) | Accuracy class combination | Rated secondary output (VA) | Surface creepage distance (MM) |
Weight (KG) | ||||
---|---|---|---|---|---|---|---|---|
1s/2s/3s/4s | 0.2(s)0.5s | 0.5 | 5P10 | 5P15 | 5P20 | |||
10-800 | 0.2(S)/0.2(S)/5P/5P 0.2(S)/0.5(S)/5p/5P 0.5(S)/0.5(S)5p/5P |
10 | 20 | 25 | 15 | 10 | 1300 |
90 |
1000 | 30 | 50 | 10 | |||||
1200-2000 | 40 | 25 | 15 |
Rated primary current (A) |
Accuracy class combination |
Rated secondary output (VA) | Surface creepage distance (MM) | Wt (KG) |
||||
---|---|---|---|---|---|---|---|---|
1s/2s/3s/4s | 0.2(S)0.5s | 0.5 | 5P10 | 5P15 | 5P20 | |||
10-15-20 |
0.2(S)/0.2(S)/5P/5P 0.2(S)/0.5(S)/5p/5P 0.5(S)/0.5(S)5p/5P |
10 |
20 | 25 | 15 | 10 | 1300 | 90 |
15-20-30 | ||||||||
20-30-40 | ||||||||
30-40-50 | ||||||||
40-50-75 | ||||||||
50-75-100 | ||||||||
75-100-150 | ||||||||
100-150-200 | ||||||||
150-200-300 | ||||||||
200-300-400 | ||||||||
300-400-500 | ||||||||
400-500-600 | ||||||||
500-600-800 | ||||||||
600-800-1200 | ||||||||
800-1200-1500 | ||||||||
1200-1500-2000 |
Rated primary current (A) |
Ith/ls (KA r.m.s.) | Idyn (KA peak) | |
---|---|---|---|
Double transformaion ratio | Single transformaion ratio | ||
10-15-20 |
10 | 2 | 5 |
15-20-30 |
15 | 3 | 7.5 |
20-30-40 |
20,25 | 4 | 10 |
30-40-50 | 30 | 6.3 | 15.7 |
40-50-75 | 40 | 9.4 | 23.6 |
50-75-100 | 50 | 12.6 | 31.5 |
75-100-150 | 75 | 15.7 | 39 |
100-150-200 | 100 | 22 | 55 |
150-200-300 | 150 | 31.5 | 78.7 |
200-300-400 |
200,250 | 47 | 118 |
300-400-500 | 300 | 63 | 157.5 |
400-500-600 |
400 | 63 | 157.5 |
500-600-800 | 500 | 80 | 200 |
600-800-1200 |
600-1200 | 80 | 200 |
800-1200-1500 |
1500-2000 | 140 | 200 |
1200-1500-2000 |