GF302B portable three phase transducer calibrator is suitable for power plant and power grid companies for the following function: metrology and testing department and instrumentation classes, national levels metrological and testing institutions, railway, petroleum, chemical industry and other large industrial and mining enterprises, scientific research units, etc. The core technology function with 32bit digital signal processor (DSP+MCU) and 24 high-speed digital A/D converters composed of high precision work frequency communication terminal. It can test the basic error of power transducer - (voltage transducer, current transducer, power factor transducer, frequency transducer, active & reactive transducer, DC transducer etc), the change caused by the influence of voltage, current, waveform, power factor, etc., and the ripple content and response time in the output DC voltage (current) of the transducer. It can also as Power calibrator, check power meter error, and as standard three phase ac voltage source and current source, or as DC power source. It is one ideal high precision calibrator in electrical laboratory.
Electrical parameters | |
---|---|
Accuracy class | 0.05% |
Power supply | Single phase AC 220V±10% or 110V±10%, 50/60Hz |
AC Voltage output | |
Range(U1,U2,U3) | 140V, 280V, 600V |
Adjusting range | (0-120)% RG |
Adjust fineness | 0.01% RG, 0.1% RG, 1% RG, 10% RG |
Accuracy | 0.05% RG |
Stability | 0.01% / 1 min |
Distortion | ≤0.2% (non-capacitive load) |
Load capacity | 25VA |
Output distortion degree | ≤0.2% or (linear load) |
AC Current output | |
Range(I1,I2,I3) | 0.2A, 1A, 10A, 20A |
Adjusting range | (0-120)% RG |
Adjust fineness | 0.01% RG, 0.1% RG, 1% RG, 10% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1 min |
Distortion | ≤0.2% (non-capacitive load) |
Load capacity | 25VA |
Output distortion degree | ≤0.2% or (linear load) |
AC Power output | |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Frequency | |
Frequency range | 40.000 - 70.000 Hz |
Resolution | 0.001 Hz |
Accuracy | 0.005 Hz |
Power factor output | |
Adjusting range | -1 ~ 0 ~ 1 |
Adjust fineness | 0.0001 |
Accuracy | 0.0005 |
Phase angle | |
Scope | 0°-359.99° |
Resolution | 0.01° |
Accuracy | 0.05° |
Voltage/Current harmonic output | |
Times | 2-31st |
Content | 0-40% |
Phase | 0-359.999 degree |
Configuration error | (10% RD + 0.1%), RD refers to the configuration value of harmonic contents |
DC Voltage output | |
Range | 5V, 65V, 500V, 1000V |
Adjusting range | (0-120)% RG |
Adjust fineness | 0.01% RG, 0.1% RG, 1% RG, 10% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25VA |
Ripple content | ≤1% |
DC Current output | |
Range | 0.1A, 0.2A, 1A, 10A, 20A |
Adjusting range | (0-120)% RG |
Adjust fineness | 0.01% RG, 0.1% RG, 1% RG, 10% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25VA |
Ripple content | ≤1% |
DC measurements | |
DC voltage measurement range | 0 to ±10V |
DC current measurement range | 0 to ±24mA |
Measurement accuracy | 0.01% RG |
Function | |
LCD display | 8.4inch touch TFT color LCD |
Data recorder | 16G, 10000sets |
Programmable | by RS232 |
Communication port | USB, RS232, 10/100M LAN |
Voltage meter test(AC/DC) | Yes |
Current meter test(AC/DC) | Yes |
Frequency meter test | Yes |
Phase angle meter test | Yes |
Power meter test | Yes |
Power factor meter test | Yes |
Synchronous meter test | Yes |
All kings of power transducer test | Yes |
As power source | Yes |
Auto test software | Yes |
Standard | |
Standard | JJG126-1995, JJG_597-2017, Q/GDW 1899-2013, DL/T1112-2009, DL/T630-1997, JJG124-2005; JJF1587-2016; IEC61010, IEC 61000, IEC 61326; IEC60736; |
Safety | |
Isolation protection | IEC 61010-1:2001 |
Measurement Category | 300 V CAT III, 600 V CAT II |
Degree of protection | IP20 |
Declaration of conformity | CE, CNAS certified |
Mechanical parameters | |
Dimensions (W×H×D) (mm) | 460x430x185 |
Weight (kg) | 25 |
Environmental conditions | |
Working temperature | 0°C to 40°C |
Storage conditions | -30°C to 60°C |
Relative humidity | ≤85% |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |